An experimental investigation of two-phase refrigerant R-410A flow distribution in plate heat exchangers

Chien Yuh Yang, Yueh Hung Lin, Guang Cheng Li

研究成果: 會議貢獻類型會議論文同行評審

摘要

This study provides an experimental observation of evaporating two-phase refrigerant 410A flow distribution in a plate heat exchanger by the method of Infra-Red Thermography. The test section was made by brazing four stainless steel chevron corrugate plates to form a three flow passages plate heat exchanger. Refrigerant flowed through the central passage of the plate heat exchanger upwardly while water flowed through the outer two side flow passages downwardly to form a counter flow. Two-phase refrigerant R-410A with vapor quality of 0.2 flowed into the heat exchanger through a small hole at various directions as the inlet distributors. An Infra-Red Thermography was installed in front of the plate to measure the plate surface temperature distribution. The test results show that the two-phase refrigerant flowed through the plates fairly uniformly over the entire heat exchanger without inlet distributor. However, while an inlet distributor was applied, since the inlet refrigerant was restricted in a small hole, this caused flow mal-distribution inside the flow passages between the plates. The inlet distributor at direction 12 provided the most uniform flow distribution and that at the direction 3 the least.

原文???core.languages.en_GB???
出版狀態已出版 - 2014
事件15th International Heat Transfer Conference, IHTC 2014 - Kyoto, Japan
持續時間: 10 8月 201415 8月 2014

???event.eventtypes.event.conference???

???event.eventtypes.event.conference???15th International Heat Transfer Conference, IHTC 2014
國家/地區Japan
城市Kyoto
期間10/08/1415/08/14

指紋

深入研究「An experimental investigation of two-phase refrigerant R-410A flow distribution in plate heat exchangers」主題。共同形成了獨特的指紋。

引用此