Effect of flow direction for the heat transfer performance of refrigerant R-410A evaporation in a plate heat exchanger

Chien Yuh Yang, Yueh Hung Lin, Fu Chen Lin

Research output: Contribution to journalArticlepeer-review

8 Scopus citations

Abstract

This article provides an experimental investigation of the effect of flow direction for refrigerant R-410A evaporated in a plate heat exchanger. Parallel-flow and counterflow arrangements with 2°C and 5°C exit superheat conditions were tested. The refrigerant entered the test section at a vapor quality of 0.24 and evaporated at a saturation temperature of 1.1°C. The experimental results were analyzed by the evaporation heat transfer coefficient and overall average heat transfer coefficient separately. The evaporation heat transfer coefficient in parallel-flow arrangement is higher than that in the case of counterflow arrangement. However, the average heat transfer coefficients are affected not only by the flow direction, but also by the exit superheat condition. The interaction of these two effects causes there to be almost no difference of the average heat transfer performance between these two flow arrangements for low exit superheat condition. While the refrigerant exit superheat is high, the overall heat transfer performance of the parallel-flow case is lower than that of the counterflow case.

Original languageEnglish
Pages (from-to)1133-1139
Number of pages7
JournalHeat Transfer Engineering
Volume34
Issue number13
DOIs
StatePublished - 2013

Fingerprint

Dive into the research topics of 'Effect of flow direction for the heat transfer performance of refrigerant R-410A evaporation in a plate heat exchanger'. Together they form a unique fingerprint.

Cite this