Projects per year
Abstract
This study developed a two-pass diverging microchannel heat exchanger to avoid flow reversal and partial dry out of HFC-245fa flow boiling in the evaporation cooling systems. It is aimed to improve the diverging microchannel heat exchangers designed by previous studies and to effectively accommodate diverging channels on a limited heating base surface. The test results showed that the maximum heat transfer coefficients in a diverging channel heat exchanger were as much as 20% higher than those in straight channel heat exchanger, while the maximum partial dry-out heat flux is 42% higher in diverging channel heat exchanger. There is no significant difference for the pressure drops in two heat exchangers at low heat fluxes before it reached the partial dry-out condition. For higher flux, the pressure drops in straight channels were higher than those in divergent channels while partial dry out. It is concluded that the two-pass diverging channel design provided higher maximum heat transfer coefficients and higher maximum heat fluxes with lower penalties of pressure drops. It could be a good design to replace the conventional straight channel heat exchanger for evaporation cooling systems.
Original language | English |
---|---|
Pages (from-to) | 1-19 |
Number of pages | 19 |
Journal | Journal of Enhanced Heat Transfer |
Volume | 31 |
Issue number | 2 |
DOIs | |
State | Published - 2024 |
Keywords
- diverging microchannel
- flow boiling heat transfer
- HFC-245fa
- partial dry out
- two-pass heat exchanger
Fingerprint
Dive into the research topics of 'DEVELOPMENT OF HEAT EXCHANGER WITH TWO-PASS DIVERGING MICROCHANNELS FOR EVAPORATION COOLING SYSTEMS'. Together they form a unique fingerprint.Projects
- 1 Finished