An in-situ performance test of liquid cooling for a server computer system

Chien Yuh Yang, Chun Ta Yeh, Pei Kang Wang, Wei Chi Liu, Edward Yu Chun Kung

Research output: Chapter in Book/Report/Conference proceedingConference contributionpeer-review

3 Scopus citations

Abstract

An IBM power series server x3350 was tested by using the liquid cooling system developed by Yang et al. [3, 4, 5]. The performance of the heat pipe based direct air cooling system equipped in the original server was also tested for comparison. Both CPU core temperature and cooling system noise level were measured in the present test. he test results of liquid cooling and direct air cooling show that the maximum average core temperature to air temperature difference (at 100% CPU loading condition) is 46.5°C for IBM original direct air cooling but only 24.8°C for liquid cooling at heat sink fan speed of 2200 rpm. At which the noise level is 59.5 and 49.5 dB respectively. While reduced the heat sink fan speed of the liquid cooling system to 1080 rpm, the core to air temperature difference slightly increased to 28.4°C, but the noise level reduced to 36.5 dB. The liquid cooling system required only 1/5 to 1/3.5 of power of the direct air cooling did. These results indicated that the liquid cooling system provides much higher cooling performance but lower noise and lower power consumption than the direct air cooling system for high power server.

Original languageEnglish
Title of host publicationInternational Microsystems Packaging Assembly and Circuits Technology Conference, IMPACT 2010 and International 3D IC Conference, Proceedings
DOIs
StatePublished - 2010
Event2010 5th International Microsystems, Packaging, Assembly and Circuits Technology Conference, IMPACT 2010 and International 3D IC Conference - Taipei, Taiwan
Duration: 20 Oct 201022 Oct 2010

Publication series

NameInternational Microsystems Packaging Assembly and Circuits Technology Conference, IMPACT 2010 and International 3D IC Conference, Proceedings

Conference

Conference2010 5th International Microsystems, Packaging, Assembly and Circuits Technology Conference, IMPACT 2010 and International 3D IC Conference
Country/TerritoryTaiwan
CityTaipei
Period20/10/1022/10/10